Bally Models with SmartVap Controller — Alarm Codes (Manual Reference)
This document applies to Bally models equipped with the SmartVap controller. Descriptions preserve manual-style wording for reference use.
PSA: Suction pressure sensor is shorted, open or pressure out of range.
SSA: Suction temperature sensor is shorted or open.
ASA: Return air temperature sensor is shorted or open.
CSA: Coil temperature sensor is shorted or open.
HSH: Superheat above upper limit.
LSH: Superheat below lower limit.
HtA: Room temperature is above ROOM TEMP + AIR TEMP DIFF + HIGH TEMP ALARM OFFSET for longer than HIGH TEMP ALARM DELAY.
LtA: Room temperature is below ROOM TEMP - LOW TEMP ALARM OFFSET for longer than LOW TEMP ALARM DELAY.
EdF: 32 defrosts or more within 48 hours.
dtt: Defrost terminated on time instead of temperature for two consecutive cycles.
dor: Door is open and room temperature is 5 degrees above ROOM TEMP + AIR TEMP DIFF for DOOR ALARM DELAY time.
CoA: ONLY FOR BONDED CONTROLLERS: No communication between controllers for one minute or more.
EA1: If AU1 IN MODE = EXT ALARM, the digital input is in an active state.
EA2: If AU2 IN MODE = EXT ALARM, the digital input is in an active state.
EA3: If AU3 IN MODE = EXT ALARM, the digital input is in an active state.
EFL: Email alert was not confirmed by email server provided after seven consecutive attempts.
A1A: AU1 temperature sensor is shorted or open.
A2A: AU2 temperature sensor is shorted or open.
A3A: AU3 temperature sensor is shorted or open.
Pdt: Max time for LPCO pumpdown exceeded.
SCC: Compressor is started an excessive number of times to maintain suction pressure.
LPA: Suction pressure dropped below expected point excessive number of times.
PrF: Basic Display is not communicating to the controller.